This page shows the data that corresponds to the HMS monitoring application. This section includes the transponder status and the attached device(s).

Monitored HMS Devices

Parameter Description
Address The transponder interface bus (TIB) address number for the monitored device. Addresses 1 to 8 are for power supplies. Address 0 is the transponder itself.
Device ID Text value of the psDeviceID (for an HMS device at address 1 to 8) or the commonModelNumber object (for the transponder at address 0).
Device Type Identifies the type of device (e.g. power supply).
Protocol Version HMS version as per the device manufacturer and model.
Software Version This is the version of the transponder's internal monitoring application.

HMS parameters

When a device is selected, the page shows the data that corresponds to the selected device on the transponder interface bus. It only shows data for one attached device at a time (Can be selected in the HMS devices table).

NOTE: This page reports the status of parameters that the device supports and for which the device is provisioned. If no alarm thresholds are defined, then the status "Nominal" is reported. If you have defined threshold values or conditions, then the transponder reports an alarm for each parameter that is outside of the nominal range. All unsupported parameters are not displayed.

Analog parameters

For all analog parameters, the tables show the current reading, the current status and, when selected, the values used for the thresholds appear in a new table. The status can be:

Status Description
Nominal When the parameter's readings are in the nominal range, the line in the table appears normal with transparent background.
HIHI or LOLO When the parameter's readings are in the HIHI (extreme high) range, or LOLO (extreme low) range, the line in the table appears in red.
HI, LO When the parameter's readings are in the HI or LO range, the line in the table appears in yellow.

Discrete parameters

For all discrete parameters, the tables show the current reading for the parameter, the current status and, when selected, the values used for the threshold appear in a new table . The status can be:

Status Description
Nominal When the parameter's readings are in the nominal range, the line in the table appears normal with transparent background.
Major Alarm When the parameter's readings indicate a major alarm, the line in the table appears in red.
Minor Alarm When the parameter's readings indicate a minor alarm, the line in the table appears in yellow.

Transponder Properties

When viewing address 0 (transponder), the transponder's HMS properties also appear in a separate table on this page, and include:

Property name Property MIB name Property description
Temperature commonInternalTemperature (1.3.6.1.4.1.5591.1.3.1.13.0) The temperature in degrees Celsius inside of the transponder itself.
Tamper Status commonTamperStatus (1.3.6.1.4.1.5591.1.3.1.12.0) Indicates the status (alarm or no Alarm of the optional Electroline tamper switch. A value is reported only if the tamper switch is used.
Craft Status commonCraftStatus (1.3.6.1.4.1.5591.1.3.1.17.0) Indicates whether the craft port (USB port on transponder) is connected or not.
Downstream Power docsIfDownchannelPower.x (1.3.6.1.2.1.10.127.1.1.1.1.6.x) The receive power level at the embedded Cable Modem.
Upstream Power docsIfCmStatusTxPower.x (1.3.6.1.2.1.10.127.1.2.2.1.3.x) The operational transmit power level for the attached upstream channel at the embedded Cable Modem.
SNR docsIfSigQSignalNoise.x (1.3.6.1.2.1.10.127.1.1.4.1.5.x) Signal/Noise ratio as perceived for the downstream channel at the embedded Cable Modem.

Input and Output Parameters (Power Supply)

This table shows the input values for the device's line voltage, current and power, and the output values for the power supply's voltage, current, power and electrical frequency.

Property name Property MIB name Property description
Input Voltage psInputVoltage.x (1.3.6.1.4.1.5591.1.4.2.1.23.x) Line voltage, if available from power supply or Electroline input sensor.
Frequency In psFrequencyIn.x (1.3.6.1.4.1.5591.1.4.2.1.35.0) Operational frequency for input line voltage.
Input Current psRMSCurrentIn.x (1.3.6.1.4.1.5591.1.4.2.1.32.0) Power supply input current in Amps RMS.
Input Power psPowerIn.x (1.3.6.1.4.1.5591.1.4.2.1.33.0) Representation of the power supply input power in Watts.
Output Voltage psOutputVoltage.x (1.3.6.1.4.1.5591.1.4.2.1.22.0) Device's output voltage shown in 1/100 Volts RMS.
Output Power psPowerOut.x (1.3.6.1.4.1.5591.1.4.2.1.30.x) Representation of the device's output power in Watts.
Output Current psOutputCurrent.x.x (1.3.6.1.4.1.5591.1.4.5.1.3.x.x) Power supply's RMS output current, in Amps, per output. Each output has an entry in the table.
Frequency Out psFrequencyOut.x (1.3.6.1.4.1.5591.1.4.2.1.31.x) Power supply's output frequency in Hz, if available.

Batteries Information (Power Supply)

This table shows the voltage and current (if supported) of each battery and the total voltage and current (if supported) of each string, as well as the current reading for the battery temperature, the battery string charge, discharge and float currents.

Property name Property MIB name Property description
Total String Voltage psTotalStringVoltage.x (1.3.6.1.4.1.5591.1.4.2.1.28.x) Total voltage of the battery string, where x is the string (1, 2, etc.)
Battery Voltage psBatteryVoltage.x.x.x (1.3.6.1.4.1.5591.1.4.4.1.4.x.x.x) Voltage of the battery, where x is the battery (1, 2, etc.) in the string. Note that for each battery, there is a separate line in this table.
String Charge Current psStringChargeCurrent.x.x (1.3.6.1.4.1.5591.1.4.3.1.3.x.x) Battery string charge RMS current, in Amps. When batteries are being discharged, this value equals 0.
String Discharge Current psStringDischargeCurrent.x.x (1.3.6.1.4.1.5591.1.4.3.1.4.x.x) Battery string discharge current (RMS) in Amps. When batteries are being charged, this value equals 0.
Float Current psStringFloat.x.x (1.3.6.1.4.1.5591.1.4.3.1.5.x.x) Battery 'float' charge current in Amps. This field will be '0' under conditions other than during actual float charging. When this field is non-zero (reporting float current), other battery current values (charge and discharge) should be discarded. If multiple strings are installed but only one measurement sensor is used, this field represents the total float current.
Temperature psTemperature.x.x (1.3.6.1.4.1.5591.1.4.6.1.3.x.x) Battery temperature as reported by the HMS device, shown in degrees Celsius.

Discrete Statuses (Power Supply)

This table shows the status of discrete alarms for the power supply at the device address you have selected.

Property name Property MIB name Property description
Major Alarm psMajorAlarm.x (1.3.6.1.4.1.5591.1.4.2.1.25.x) Indicates the presence or absence of a major alarm.
Minor Alarm psMinorAlarm.x (1.3.6.1.4.1.5591.1.4.2.1.26.x) Indicates the presence or absence of a minor alarm.
Tamper psTamper.x (1.3.6.1.4.1.5591.1.4.2.1.27.x) Indicates the whether the tamper switch is compromised or intact.
Input Voltage Presence psInputVoltagePresence.x (1.3.6.1.4.1.5591.1.4.2.1.34.x) Indicates whether AC line voltage is present or lost. This object only appears if input voltage support is set to Discrete. Otherwise, analog readings for input voltage may appear in the Analog Alarm section, if supported.

XM2 Extension Properties (Power Supply)

This table shows the status of XM2-specific discrete attributes for the power supply at the device address you have selected.

Property name Property MIB name Property description
General Status amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.1) General status, could be a major or a minor alarm or everything is Ok.
Self Test Fail amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.2) Indicates that the Self test failed.
Low Battery Volts amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.3) Indicates Low battery voltage.
High Battery Volts amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.4) Indicates High battery voltage.
No Batteries amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.5) Indicates that No batteries are connected.
Batt Temp Probe amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.6) Battery temperature probe indicates an XM-2 temperature probe has failed or is not connected.
Line Isolation amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.7) Line isolation circuitry status.
Output Failure amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.8) AC output failure, open or short detected by power supply.
Output Overload amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.9) Indicates XM2 is overloaded. Power supply will shut down and restart periodically.
Output 1 Tripped amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.10) Ouput1 is blocked because the current is greater than the Max current value limit.
Output 2 Tripped amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.11) Ouput2 is blocked because the current is greater than the Max current value limit.
Charger Failure amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.12) Charger has failed or was shut down due to problem such as battery over-temp
Input Failure amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.13) Indicates AC input failure
Inv Disconnected amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.14) Inverter disconnected.
Inverter Temp amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.15) Inverter heat sink over-temperature.
Tap Switch amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.16) TAP switch option (available or not available) (YES/NO).
PIM Option amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.17) Protective interface module (available or not available) (YES/NO).
N+1 In Use amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.26) N+1 system has been activated.
Tap Fuse Fail amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.29) Fuse failure on tap switch option board.
Config Error amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.30) XM2 has detected that it is improperly configured.
N+1 Fault amiCibDiscEnum.12.1.x (1.3.6.1.4.1.5802.1.3.1.2.5.1.17.1.1.1.1.1.6.31) Fault in N+1 system.

Fiber Node

This table shows the status of various properties for the Fiber Node at the device address you have selected.

Property name Property MIB name Property description
Tamper Status commonTamperStatus (1.3.6.1.4.1.5591.1.3.1.12.0) Indicates the status (alarm or no Alarm of the optional Electroline tamper switch. A value is reported only if the tamper switch is used.
     
  Return Laser Table  
RTXState globalFnReturnLaserState (1.3.6.1.4.1.5802.1.3.1.2.5.1.14.1.2.1.2) Report the state of this return transmitter. If the state is available, this return transmitter is plugged in the module. If the state is unavailable, this return transmitter is not plugged in the module.
ReturnLaserType fnReturnLaserType (1.3.6.1.4.1.5591.1.5.3.1.5) Type of return laser. Some valid values are: unisolated FP, isolated FP, uncooled DFB, cooled DFB, ITU(up to 32 colors).
ReturnLaserOpticalPower fnReturnLaserOpticalPower (1.3.6.1.4.1.5591.1.5.3.1.7) Returns the optical power on the return laser. Units 0.1 milliWatts. This item requires an entry in the properties MIB
ReturnLaserRFActive fnReturnLaserRFActive (1.3.6.1.4.1.5591.1.5.3.1.8) Returns the RF Active index associated with this return laser. If the RF active is undetermined, the value will be 0, and is NOT a valid index into the RF active table. Write access to this variable should only be provided if the RF Active path for this module can not be automatically determined and configured
     
  Optical Receiver table  
OpticalReceiverType globalFnOpticalReceiverType (1.3.6.1.4.1.5802.1.3.1.2.5.1.14.1.6.1.3) Type of optical receiver. Some valid values are: , standard frx,low input frx.
OpticalReceiverPower fnReturnLaserOpticalPower (1.3.6.1.4.1.5591.1.5.3.1.7) Returns the optical power on the return laser. Units 0.1 milliWatts. This item requires an entry in the properties MIB.
OpticalReceiverState fnOpticalReceiverState (1.3.6.1.4.1.5591.1.5.5.1.3) Reports the state of this optical receiver
OpticalReceiverRFActive fnOpticalReceiverRFActive (1.3.6.1.4.1.5591.1.5.5.1.4) Returns the RF Active index associated with this optical receiver. If the RF active is undetermined, the value will be 0, and is NOT a valid index into the RF active table. Write access to this variable should only be provided if the RF Active path for this module can not be automatically determined and configured.
OpticalReceiverAGCState globalFnOpticalReceiverAGCState (1.3.6.1.4.1.5802.1.3.1.2.5.1.14.1.4) Reports the optical receivers AGC state. 0 = Optical receiver1 AGC OFF;Optical receiver2 AGC OFF 1 = Optical receiver1 AGC OFF;Optical receiver2 AGC ON 2 = Optical receiver1 AGC ON;Optical receiver2 AGC OFF 3 = Optical receiver1 AGC ON;Optical receiver2 AGC ON.
     
  RF Port Table  
RFPortRFActive fnRFPortRFActive (1.3.6.1.4.1.5591.1.5.11.1.5) Returns the RF Active index associated with this RF Port
RFPortName fnRFPortName (1.3.6.1.4.1.5591.1.5.11.1.6) Physical name of Port. Some examples are Port 1 and Port 2. This name is put into the alarmText object used by hmsAlarmTrap when alarms are generated by objects in this table.
RFPortReverseAttState
     
  Optical Receiver AB Switch Table  
FRXABSwitchState fnOpticalReceiverABSwitchState (1.3.6.1.4.1.5591.1.5.13.1.4) Reports the state of the AB switch. pathA indicates that the switch is being fed by feed A. pathB indicates that the switch is being fed by feed B. This item requires an entry in the discrete properties MIB.
     
  RF Router Table  
Forward RF Router: downStreamSwitchState globalFnRFRouterDownstreamSwitchState (1.3.6.1.4.1.5802.1.3.1.2.5.1.14.1.10.1.3) Reports the state of the downstream redundant & segmentation switch. unavailable(0) indicates that the switch is unavailable. redundantMode(1) indicates that the switch is in redundant mode. segmentation(2) indicates that the switch is in segmentation mode.
Reverse RF Router: upstreamSwitchState globalFnRFRouterUptreamSwitchState (1.3.6.1.4.1.5802.1.3.1.2.5.1.14.1.10.1.7) Reports the state of the upstream redundant & segmentation switch state. unavailable(0) indicates that the switch is unavailable. redundantMode(1) indicates that the switch is in redundant mode. segmentation(2) indicates that the switch is in segmentation mode.
     
  AC Power Table  
Type Of Power Supply
     
  DC Power Table  
DCPowerVoltage fnDCPowerVoltage (1.3.6.1.4.1.5591.1.5.19.1.2) Returns the regulated power voltage. Units in 0.1 Volts. This item requires an entry in the properties MIB. This object shall report alarms using the value of fnDCPowerName in the alarmText object in the hmsAlarmEvent Trap.
DCPowerName fnDCPowerName (1.3.6.1.4.1.5591.1.5.19.1.4) Identifies the Physical name of the Power Supply. For example: 24 VDC Supply A Actual value of this field is vendor specific, at a minimum it shall identify the nominal voltage expected and distinguish the supplies from one another. If a single PHYSICAL supply provides multiple voltages, each voltage shall have its own entry in this table, with an appropriate name. This name is put into the alarmText object in the hmsAlarmEvent Trap when alarms are generated by objects in this table.